| PTTS | CS-2HF | CW-16HF | |
|---|---|---|---|
| Function | Basic (Not networked) | Smart (Networked) | Switched (Networked) with outlet ON/OFF/Reboot control |
| Total Number of Outlets | (8) IEC C13 | (2) IEC C19 | 120 V: (16) NEMA 5-20R 200-240 V: (16) IEC C13 |
| Power Distribution Under Normal Operation | Primary selector switch to supply power to all 8 outlets | Load sharing. Input A powers Outlet A, Input B powers Outlet B | Load sharing. Input A powers Outlet A, Input B powers Outlet B |
| Input Power Cord | Sold separately | 16/20 A version: sold separately 30/32 A version: hardwired |
16/20 A version: sold separately 30/32 A version: hardwired |
| Input Power Options | 100-240V; 20A (user accessible selector switch) | 208 V; 20 A or 30 A 230 V; 16 A or 32 A |
120 V; 20 A or 30 A 208 V; 20 A or 30 A 230 V; 16 A or 32 A |
| Phase Synchronization Required? | Yes | Yes | Yes |
| Form Factor | 1U, Horizontal Mount | 1U, Horizontal Mount | 2U, Horizontal Mount |
| Temperature/Humidity Sensors | No | Up to 2 (P/N EMTH-1-1) | Up to 2 (P/N EMTH-1-1) |
| Input Current Monitoring | No | Yes | Yes |
| Input Current LEDs | No | One per input feed | One per input feed |
| Expansion Unit to Share One IP Address | No | Yes | Yes |
| Branch Circuit Protection | Internally fused | Internally fused | User-resettable breakers |